產(chǎn)品概述 Product overview
GCS 型低壓抽出式開關(guān)柜,適用于發(fā)電廠、石油、化工、冶金、紡織、高層建筑等行業(yè)的配電系統(tǒng)。在大型發(fā)電廠、石化系統(tǒng)等自動(dòng)化程度高,要求與計(jì)算機(jī)接口的場所,作為三相交流頻率為 50(60)Hz、額定工作電壓為 400V、660V,額定電流為 5000A 及以下的發(fā)、供電系統(tǒng)中的配電、電動(dòng)機(jī)集中控制、無功功率補(bǔ)償使用的低壓成套配電裝置。
裝置的設(shè)計(jì)符合下列標(biāo)準(zhǔn):IEC439-1《低壓成套開關(guān)和控制設(shè)備》GB7251《低壓成套開關(guān)設(shè)備》。
GCS type low-voltage draw-out switchgear is suitable for power distribution systems in power plants, petroleum, chemical industry, metallurgy, textile, high-rise buildings and other industries. In large power plants, petrochemical systems and other places with high degree of automation and computer interface requirements, it is used as a low-voltage complete power distribution device for power distribution, centralized motor control and reactive power compensation in power generation and supply systems with three-phase AC frequency of 50(60)Hz, rated working voltages of 400V and 660V and rated current of 5000A or less.
The design of the device conforms to the following standards: IEC439-1 《Low Voltage Complete Switchgear and Control Equipment》 GB7251 《Low Voltage Complete Switchgear》.
正常使用環(huán)境 Normal operating environment
◇ 周圍空氣溫度不高于 +40℃, 不低于 -5℃ , 24 小時(shí)內(nèi)平均溫度不得高于 +35℃。超過時(shí),需根據(jù)實(shí)際情況降容運(yùn)行;
◇ 戶內(nèi)使用,使用地點(diǎn)的海拔高度不得超過 2000m;
◇ 周圍空氣相對(duì)濕度在溫度為 +40℃時(shí)不超過 50%,在較低溫度時(shí)允許有較大的相對(duì)濕度,如 +20℃時(shí)為 90%,應(yīng)考慮到由于溫度的變化可能會(huì)偶然產(chǎn)生凝露的影響;
◇ 裝置安裝時(shí)與垂直面的傾斜度不超過 5°, 且整組柜列相對(duì)平整 ( 符合 GBJ232-82 標(biāo)準(zhǔn) );
◇ 裝置應(yīng)安裝在無劇烈震動(dòng)和沖擊以及不足以使電器元件受到不應(yīng)有腐蝕的場所 ;
◇ 用戶有特別要求時(shí),可以與制造廠協(xié)商解決。
◇ Ambient air temperature shall not be higher than +40℃ , not lower than-5℃ , and the average temperature within 24 hours shall not be higher than
+35℃ . In case of exceeding, the capacity shall be reduced according to the actual situation.
◇ For indoor use, the altitude of the place of use shall not exceed 2000 m;
◇ The relative humidity of the ambient air shall not exceed 50% at the highest temperature of +40℃ , and relatively high relative humidity is allowed at lower temperature, such as 90% at +20℃ , which shall be considered Due to changes in temperature, condensation may occasionally occur.
◇ When the device is installed, the inclination to the vertical plane shall not exceed 5, and the whole set of cabinet columns shall be relatively flat (in line with GBJ232-82 standard);
◇ The device shall be installed in a place free from severe vibration and impact and insufficient to expose electrical components to corrosion.
◇ When users have special requirements, they can negotiate with the manufacturer.